Introduction:
The chilled water fan wall unit of our CMC series is a member large-scale computer room air conditioner, providing precise temperature and humidity control for the computer room. Usually, it combines with chillers, pumps, chilled water pipelines, and other components as a cooling system. High reliability, stability, and energy-saving, helping to build the next generation of green data centers.
Application:
● Medium, large-scale switch computer room
● Computer room and prefabricated data center
● Industry control room
● Standard test room and calibration center
Features:
● Efficient
1. Support higher chilled water temperature up to 20℃, improve chiller efficiency, increase free-cooling
duration, for lower PUE.
2. High-efficiency wet-film humidifier, more stable and energy-saving, compared to electrodes and far-infrared humidification, it saves 99%+ energy without additional heating.
● Reliable
1. Adopt EC centrifugal fan, step-less speed regulation, and automatic regulation of cooling capacity and airflow.
2. Multiple protection, such as overvoltage and undervoltage protection, delayed start protection, multi-level
password protection, water leakage protection, etc.
3. Group control for 32 units at maximum, flexible configuration.
Technical Data:
Technical Specification |
|
Total Cooling Capacity (kW) |
210 |
Sensible Cooling Capacity (kW) |
210 |
Air Supply |
Horizontal |
Air Flow (m³/h) |
60000 |
ESP (Pa) |
0-300Pa |
Refrigerant Type |
Chilled Water |
EER |
≥10 |
Reheating Capacity (kW) |
24 |
Humidification (kg/h) |
10 |
Air Filter Class |
G4 |
Dimension: H×W×D (mm) |
2200 ×2000 ×1200 |
* Cooling capacity condition: Inlet/outlet water temperature=20 ºC/28 ºC, Return air dry bulb temperature=36 ºC/24% RH, Air supply=24 ºC (± 1ºC) , ESP=100Pa. |