Row-Based Air-Cooled Air Conditioner for In-row Cooling System

Products

description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Features

Introduction:

 

CRA Row-Based Air-Cooled Aircon is installed in close proximity to heat sources, minimizing the length of the cold airflow path and accurately handling the sensible heat generated by servers.

 

Application:

 

Small-to-medium-sized Data Centers

Modular Data Centers

Cabinet Row Cooling (or heat) Channel Retrofitting

Medium-to-high heat-density Communication Equipment

Computer Rooms

 

Features:

 

The key components are selected from well-known brands.

A fully EC variable frequency design, automatically adjusting cooling and airflow output.

The humidification component has zero power consumption and is energy-efficient.

The "full cabinet-style straight or U-shaped" evaporator has a large area and low air resistance.

The high-return air temperature design significantly improves energy efficiency.

Three operation modes automatically switch and adjust in real-time.

The pump cabinet system is designed in series, highly integrated, and more energy-efficient.

The pump cabinet is integrated on the outside, eliminating the need for separate space.

It integrates efficient energy-saving algorithms and supports group control, rotation, and cascading. 

 

Technical Data:

 

CRA Row-Based Air-cooled Aircon

Indoor unit model

CRA3012

CRA3025

CRA3040

CRA3050

CRA3060

Main power supply

380V3Ph~50Hz

Air supply

Front air supply

Performance   parameter

Cooling capacity(kW)

12.5

25

40

50

60

Sensible capacity(kW)

12.5

25

40

50

60

Max. operation current FLA(A)

27.5

37

50.2

54

57.2

Compressor  QTY

1

Fan Type

EC Centrifuge fan

Fan QTY

3

6

2

3

3

Circulating air volume(m³/h)

3000

5000

8000

10800

12000

Heating capacity(kW)

2

3

6

9

9

Humidification(kg/h)

1

1.5

3

4.5

4.5

Connecting pipe size(30m)

Liquid  pipe(mm)

9.52

15.88

15.88

15.88

15.88

Gas   pipe(mm)

19.05

22

22

22

22

Humidification inlet pipe (Internal thread)

G3/4"

Water pump drain pipe(mm)

ID9.53*OD17.02

Natural drain pipe(mm)

ID16*0D24

Unit dimension and weight

Dimension-W(mm)

300

300

600

600

600

Dimension-D(mm)

1100/1200

Dimension-H(mm)

2000/2200

Weight(kg)

190

210

250

310

310

Outdoor unit performance parameter(40°℃)

Flat-plate outdoor unit model

CSTO13SP

CMTO38SP

CMT055SP

CMT077SP

CMTO88SP

Centralized outdoor unit model

N/A

CMTO38SF

CMT055SF

CMT077SF

CMT088SF

Performance   parameter(45℃)

Flat-plate outdoor unit model

N/A

CMTO44SP

CMT066SP

CMTO88SP

CMTO99SP

Centralized outdoor unit model

N/A

CMTO44SF

CMT066SF

CMT088SF

CMT099SF

Electronic element specification

Air switch recommended(A)

40

40

63

63

63

Indoor power cable diameter(mm²)

4*6.0+1*6.0

4*6.0+1*6.0

4*16+1*16

4*16+1*16

4*16+1*16

Remark:
1.Standard working conditions: indoor return air temperature 37°℃, RH 24%, outdoor ambient temperature 35℃,ESP=10Pa;
2. Only cooling+ electric heating or constant temperature and humidity type can be selected. The maximum working current and the recommended air switch are configured according to the constant temperature and humidity unit.
3.The table above is only part of the parameters, and the specific configuration is subject to the nameplate.

 

Downloads

  •  
  •  
  •