Two-Phase Dielectric Fluid

Products

description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Information

Product Description
Two-Phase Dielectric Fluid is excellent insulation immersion fluid. This product is a two-phase immersion coolant and can be used directly.

Features and Usages
Excellent electrical insulation performance, to ensure the safety performance of data centres and energy storage power stations, voltage resistance of 35KV or more;
• Low boiling point, easy to vaporise, high latent heat of phase change, low kinematic viscosity, good fluidity, improve the level of submerged temperature control system temperature control;
• High thermal stability, will not burn or explode during use, ensuring that the battery will not burn when the temperature is too high, improving the safety of data centres and energy storage power stations;
• Excellent metal anti-corrosion performance and non-metallic compatibility, extending the service life of the submerged temperature control system;
• Excellent anti-freezing performance, preventing equipment damage caused by liquid freezing and expansion;
• Good environmental performance, does not contain toxic substances, harmless to the environment and personnel, in line with environmental requirements.

Application
Temperature control systems for immersed data centres and immersed energy storage batteries.

Typical Data
PROPERTIES
TYPICAL DATA
Appearance
Colourless, odourless, transparent liquid
Density(25℃),g/cm3
1.6
Kinematic viscosity(25℃)/(mm2/s)
0.4
Boiling point/℃(atmospheric)
49.2
Freezing point/℃
-108
Latent heat of evaporation/(kJ/kg)
88
Flash point/℃
Not applicable (non-flammable)
Specific heat capacity/(J/(kg.℃))
1013
Thermal conductivity/(W/(m.℃))
0.063
Dielectric strength/kV
39.9kV
Resistivity/(Ω·cm)
7.174*10^12
Dielectric constant
2.01
Ozone Depletion Potential(ODP)
0
Global Greenhouse Potential (GWP)
1