Introduction:
The CDA rack-mounted air conditioning unit is a cabinet-level temperature control product designed specifically for high-density data centers. It is closely attached to the rack of the server cabinets, allowing for precise handling of high sensible heat generated by the servers within the cabinets. This effectively prevents the occurrence of localized hot spots and contributes to the continuous development of green data centers.
Application:
● Computer Rooms, especially the Small/miniature distributed
● Data centers, Modular data centers
● IT Cabinets for blade servers
● Medium-to-high heat-density Communication Equipment
Features:
● The 5kW model is only 5U high, maximizing available space in the cabinet.
● Support top temperature sensing management in the cabinet to eliminate localized hotspots.
● Multiple drainage and anti-backflow designs prevent cabinet flooding.
● The refrigerant capacity intelligently self-detects and provides smart alerts.
● A high-efficiency variable frequency compressor and ultra-precise PID control technology.
● Smooth throttle adjustment is achieved with an electronic expansion valve.
● The EC centrifugal fans can dynamically adjust airflow output in real time.
● Wide power grid adaptability, meeting a voltage range of 20%.
Technical Data:
CDA Rack Aircon |
|||||||
Indoor unit model |
CDA0004 |
CDA0005 |
CDA0008 |
CDA0013 |
CDA0004 |
CDA0005 |
CDA0008 |
Dimension-D (mm) |
760 |
400 |
|||||
Main power supply |
220V/1Ph~50Hz |
||||||
Air supply |
3 side air supply |
||||||
Unit performance parameter |
|||||||
Cooling capacity(kW) |
3.5 |
5 |
7.5 |
12.5 |
3.5 |
5 |
7.5 |
Sensible capacity(kW) |
3.5 |
5 |
7.5 |
12.5 |
3.5 |
5 |
7.5 |
Max. operation current FLA(A) |
11.5 |
16.5 |
20.0 |
35 |
11.5 |
16.5 |
20 |
Compressor QTY |
1 |
||||||
Fan type |
EC centrifugal fan |
||||||
Fan QTY |
2 |
2 |
1 |
2 |
1 |
1 |
2 |
Circulating air volume(m³/h) |
800 |
1100 |
1650 |
2200 |
800 |
1100 |
1650 |
Heating capacity(kW) |
1 |
1 |
1 |
2 |
1 |
1 |
1 |
Humidification(kg/h) |
1 |
1 |
1.5 |
3 |
|
|
|
Connecting pipe size |
|||||||
Liquid pipe(mm) |
9.52 |
9.52 |
12.7 |
12.7 |
9.52 |
9.52 |
12.7 |
Gas pipe(mm) |
15.88 |
15.88 |
19.05 |
19.05 |
15.88 |
15.88 |
19.05 |
Humidification inlet pipe (Internal thread) |
OD20*G3/4" |
||||||
Water pump drain pipe(mm) |
PU pipel D 5*0D8 |
||||||
Natural drain pipe(mm) |
Silicone hoselD10*OD14 |
||||||
Unit dimension and weight |
|||||||
Dimension-W(mm) |
443 |
443 |
443 |
443 |
444 |
444 |
444 |
Dimension-D(mm) |
715 |
715 |
715 |
715 |
395 |
395 |
395 |
Dimension-H(mm) |
218 |
218 |
351 |
440 |
352 |
352 |
529 |
Weight(kg) |
27 |
28 |
36 |
42 |
25 |
26 |
36 |
Outdoor unit performance parameter |
|||||||
Outdoor unit model |
CDT005SP |
CDT007SP |
CDT010SP |
CDT016SP |
CDT005SP |
CDT007SP |
CDT010SP |
Dimension-W(mm) |
794 |
794 |
1045 |
1045 |
794 |
794 |
1045 |
Dimension-D(mm) |
310 |
310 |
431 |
431 |
310 |
310 |
431 |
Dimension-H(mm) |
537 |
537 |
760 |
1375 |
537 |
537 |
760 |
Weight(kg) |
30 |
34 |
60 |
85 |
30 |
34 |
60 |
Electronic element specification |
|||||||
Air switch recommended (A) |
16 |
25 |
25 |
40 |
16 |
25 |
25 |
Indoor power cable diameter |
(L、N、PE)3×2.5 |
(L、N、PE)3×2.5 |
(L、N、PE)3×4 |
(L、N、PE)3×6 |
(L、N、PE)3×2.5 |
(L、N、PE)3×2.5 |
(L、N、PE)3×4 |
Outdoor power cable diameter |
(L、N、PE)3×1.5 |
(L、N、PE)3×2.5 |
(L、N、PE)3×2.5 |
(L、N、PE)3×4 |
(L、N、PE)3×1.5 |
(L、N、PE)3×2.5 |
(L、N、PE)3×2.5 |