CNA Precision Air Conclitioner for Computer Room

Products

description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
Features

Introduction:

 

This type of precision aircon is in our CNA Dual-Engine Series and features two independent refrigeration cycles. These systems offer flexible switching, and autonomous rotation, and serve as backups for each other. They provide professional advantages with high reliability and energy efficiency, capable of meeting the high cooling demands of continuous operation in data center environments.

 

Application:

 

  Small and medium-sized computer rooms

  Four electrical rooms

  Battery rooms

  Equipment rooms

   High-end communication base stations, and various types of equipment rooms

 

Features:

 

Dual-engine drive, stable and reliable.

 The entire system has a standard sensible heat ratio higher than 0.9, verified through CFD simulation and designed for minimal airflow resistance.

 Upper and lower parabolic airflow design enables air routing across obstructing equipment.

 Built-in compressors greatly reduce the footprint.

 Remote monitoring and management allow for unmanned operation.

 Capable of operating in outdoor temperatures ranging from -25°C to 48°C.

 Supports electrical metering.

 

Technical Data:

 

CNA Precision Aircon for Computer Room

Indoor unit model

CNA1008

CNA1013

CNA1020

Main power supply

380V 3Ph~50Hz

Air supply

Up and front air supply

Performance parameter

Cooling capacity(kW)

8.0

13.0

20.1

Sensible capacity(kW)

7.36

12.22

18.1

Max. operation current FLA(A)

15

18.7

25.0

Compressor  QTY

1

Fan type

DC axial flow fan

Fan QTY

2

Circulating  air  volume(m³/h)

2800

3500

5000

Heating capacity(kW)

2

2

3

Humidification(kg/h)

2                                  2                                  3

Connecting pipe size

Liquid pipe(mm)

6.35

9.52

12.7

Gas  pipe(mm)

15.88

19.05

19.05

Humidification  inlet  pipe

(Internal  thread)

G3/4

Drain pipe

Inner diameter 19mm, outer diameter 25mm, Metal hose clamp connection

Indoor unit dimension and weight

Dimension-W(mm)

510

510

580

Dimension-D(mm)

425

425

450

Dimension-H(mm)

1887

1887

1950

Weight(kg)

93

108

148

Outdoor unit performance parameter

Outdoor unit model

CSTO08SP1A

CSTO13SP1A

CSTO20SP1A

Dimension-W(mm)

728

728

1020

Dimension-D(mm)

405

Dimension-H(mm)

762

1370

1370

Weight(kg)

34

53

74

Electronic   element   specification

Air switch(recommended)(A)

25

25

32

Indoor power cable diameter(mm²)

4*4.0+1*4.0

4*4.0+1*4.0

4*6.0+1*6.0

Outdoor power cable diameter (mm²)

2*1.0+1*1.0

 